NOTES:
1. ENTIRE INSTALLATION IS RATED FOR LOCAL SOIL & WIND CONDITIONS.
2. SUPPLY AND INSTALL NON-CONDUCTIVE BOLLARDS IN LOCATIONS AS REQUIRED TO PROTECT URD AND SMSB TO SUPERINTENDENTS’ APPROVAL.
3. UNDERTAKE SITE INVESTIGATIONS TO DETERMINE EXACT LOCATION OF ALL EXISTING UNDERGROUND CABLING IN VICINITY. IF PROPOSED LOCATIONS OF BOLLARDS IS COMPROMISED BY EXISTING UNDERGROUND ASSETS, REPORT TO SUPERINTENDENT FOR DIRECTION.
4. PROVIDE SURVEY WITH PROPOSED FINAL LOCATION OF BOLLARDS TO SUPERINTENDENT FOR APPROVAL PRIOR TO COMMENCING ANY POTHOLES AND/OR PLACING ORDERS FOR BOLLARDS
5. NON-METALLIC BOLLARDS SHALL BE CIRCULAR 150 mm X 1250 mm TALL, ROUND TOP. ZERO CIVIL, B150, ZERO CIVIL, B150, + IRR-150 OR APPROVED EQUIVALENT.
6. BOLLARDS SHALL BE YELLOW WITH RED/WHITE REFLECTIVE BAND
7. BOLLARDS ARE MANUFACTURED BY AUSTRALIAN COMPANY THAT SUPPLIES NON-METALLIC BOLLARDS FOR PROTECTION OF ELECTRICAL ASSETS. USE SPECIFIED FITTINGS OR APPROVED EQUIVALENT e.g. SMART UBRAN PTY LTD / ZERO CIVIL - CONTACT LISA KASTEN (0414 628 511)
8. INSTALL BOLLARDS TO MANUFACTURES RECOMMENDATION, TO SUPERINTENDENTS’ APPROVAL.
9. PROVIDE CONCRETE FOOTING MINIMUM 400mm DEEP AND 400mm SQUARE, FOR SOLID CONCRETE FOOTINGS AND 700 X 400 mm FOR FREE STANDING INSTALLATIONS, BELLED OUT AT BASE WHEN IN NON- COMPACTED SOIL.
10. CONCRETE BASE SHALL BE 30MPa OR GREATER, DO NOT USE RAPID SET AS IT IS NOT IMPACT RESISTANT.Â
11. DO NOT USE FLEXIBLE GROUT.
12. TAPER MUST FINISH FLUSH WITH SOCKET, AND SOCKET MUST FINISH FLUSH WITH GROUND LEVEL SO THEY ARE NOT DAMAGED ON IMPACT.
13. COLOUR OF FOUNDATION TO MATCH WALKWAYS - CONFIRM FINISH WITH SUPERINTENDENT PRIOR TO POURING FOUNDATION.
14. PROVIDE SHOP DRAWING TO SUPERINTENDENT FOR APPROVAL.Â
15. WE RECOMMEND A MAXIMUM OF 1.5 M SPACING OF BOLLARDS